<body><script type="text/javascript"> function setAttributeOnload(object, attribute, val) { if(window.addEventListener) { window.addEventListener('load', function(){ object[attribute] = val; }, false); } else { window.attachEvent('onload', function(){ object[attribute] = val; }); } } </script> <div id="navbar-iframe-container"></div> <script type="text/javascript" src="https://apis.google.com/js/platform.js"></script> <script type="text/javascript"> gapi.load("gapi.iframes:gapi.iframes.style.bubble", function() { if (gapi.iframes && gapi.iframes.getContext) { gapi.iframes.getContext().openChild({ url: 'https://www.blogger.com/navbar/8947368?origin\x3dhttps://southbrucepeninsula.blogspot.com', where: document.getElementById("navbar-iframe-container"), id: "navbar-iframe" }); } }); </script>

Wednesday, March 15, 2006

Wiarton Water Treatment Plant Annual Report 2004

Drinking-Water Systems Regulation O. Reg. 170/03

Part III Form 2
Section 11. ANNUAL REPORT.

Drinking-Water System Number: 220002681
Wiarton Water Treatment Plant
Drinking-Water System Name:
Town of South Bruce Peninsula
Drinking-Water System Owner:
Large Municipal Residential
Drinking-Water System Category:
Jan 1/04 to Dec 31/04
Period being reported:

Complete if your Category is Large Municipal Complete for all other Categories.
Residential or Small Municipal Residential

Does your Drinking-Water System serve Number of Designated Facilities served:
more than 10,000 people? Yes [ ] No [ X ]

Is your annual report available to the public Did you provide a copy of your annual
at no charge on a web site on the Internet? report to all Designated Facilities you
Yes [ X ] No [ ] serve?
Yes [ ] No [ ]
Location where Summary Report required
under O. Reg. 170/03 Schedule 22 will be Number of Interested Authorities you
available for inspection. report to:
Town of South Bruce Peninsula
Did you provide a copy of your annual
315 George Street
report to all Interested Authorities you
Wiarton, Ontario
report to for each Designated Facility?
N0H 2T0
Yes [ ] No [ ]
519 534 1400

Note: For the following tables below, additional rows or columns may be added or an
appendix may be attached to the report

List all Drinking-Water Systems (if any), which receive all of their drinking water from
your system:
Drinking Water System Name Drinking Water System Number
Oxidant Water 260004215

Did you provide a copy of your annual report to all Drinking-Water System owners
that are connected to you and to whom you provide all of its drinking water?
Yes [ ] No [ ]

Drinking-Water Systems Regulations Page 1 of 7
Part III ­ Form 2 (PIBS 4435E Version January 2005)
Drinking-Water Systems Regulation O. Reg. 170/03

Indicate how you notified system users that your annual report is available, and is free
of charge.
[ X ] Public access/notice via the web
[ X ] Public access/notice via Government Office
[ ] Public access/notice via a newspaper
[ ] Public access/notice via Public Request
[ ] Public access/notice via a Public Library
[ ] Public access/notice via other method _______________________________________

Describe your Drinking-Water System
Class 2 Distribution, Class 3 Treatment
Raw water intake (450mm polyethylene, extending 200m into Colpoy Bay) enters plant through a mechanical
traveling screen. There is also a back-up 450mm intake parallel to the main intake that extends 60m into Colpoy
Bay. Zebra mussel control is installed at the intake crib and utilizes sodium hypochlorite on both intake lines.
Pre-chlorination is also available at the raw water well inlet. The two compartment raw water well has two
vertical turbine low lift pumps (31.3 L/s) installed in each compartment. Raw water is pumped to flocculation
tanks and polyaluminum chloride is injected into the raw water feed line at a flash mixer prior to entering the
two floc tanks.

Powdered activated carbon can also be injected in this line upstream of the mixer. Sodium hypochlorite can also
be injected prior to the mixer if required. Water flows from the floc tanks to the two dual media filters. The
filtered water then passes into a dual-compartment clear well/contact chamber/ backwash storage reservoir
(capacity of approx. 809m3). Two high lift pumps (capacity of 60 L/s each @ 77.7m TDH) supply water to the
distribution system from the water treatment plant. The plant has a filter backwash system that utilizes water
stored in the clearwell. Two backwash pumps with a capacity of 167.8 L/s each and four surface agitators
provide filter washing when required. Backwash wastewater is stored in two surge tanks with a total volume of
512 m3. Two waste transfer pumps pump the surge tank contents to a sedimentation tank and with the addition
of a polymer the waste sludge is transferred to an on-site sewage pump station where the plant wastes are
pumped to the sanitary sewage system. Two Ultraviolet (UV) disinfection reactors located on the high lift
discharge header. Each unit is designed to provide a minimum pass through dose of 40mJ/cm2 at a minimum
UVT of 90% at a maximum flow rate of 87.4 L/sec.

Potable water produced by the plant is fed directly to the distribution system with the excess water filling the
2894 m3 water standpipe which supplies pressure to the system and controls the water plant operation by preset
level controls in the tower. A booster pump station located at the water storage tower site supplies additional
pressure to the higher elevations located in the northwest section of Wiarton.

List all water treatment chemicals used over this reporting period
Sodium Hypochlorite 12%
Polyaluminum Chloride
Sodium Metabisulphate

Were any significant expenses incurred to?
[X] Install required equipment
[X] Repair required equipment
[X] Replace required equipment

Drinking-Water Systems Regulations Page 2 of 7
Part III ­ Form 2 (PIBS 4435E Version January 2005)
Drinking-Water Systems Regulation O. Reg. 170/03

Please provide a brief description and a breakdown of monetary expenses incurred
Item Date Cost

SCADA Updates, Electrical drawings June 14 $6,727.50

Service Contract, Telephone support March 3 $345.00

Cathodic Protection Anodes November 25 $5,714.35

Clearwell Level Alarms October 1 $1,380.00

Anthracite Filter Media June 21 $2,834.75

Low Voltage Capacitor July 12 $798.33

Install/purchase 2 pressure switches June 10 $975.76

HMI Alarms/PLC Control Updates March - May $3,795.00

PLC Program & SCADA Updates March ­ May $3,105.00

Analyzer Configuration April ­ May $2,530.00

Water Tower/Standpipe Repairs June 14 $5,220.84

Provide details on the notices submitted in accordance with subsection 18(1) of the Safe
Drinking-Water Act or section 16-4 of Schedule 16 of O.Reg.170/03 and reported to
Spills Action Centre
Incident Date Parameter Result Unit of Corrective Action Corrective
Measure Action Date
May 8/04 UV dose <40 MJ/cm2 Place backup May 8/04
AWQI UV system into
#25816 service
May 9/04 UV dose <40 MJ/cm2 Restart highlift May 9/04
AWQI pump mannually
#25838
May 11/04 UV dose <40 MJ/cm2 Place backup May 11/04
AWQI UV system into
#25873 service
June 18/04 UV dose <40 MJ/cm2 Restart UV June 18/04
AWQI system put into
#27908 service
June 19/04 UV dose <40 MJ/cm2 Chronic UV June 19/04
AWQI problem being
#27959 investigated by
UV supplier

Drinking-Water Systems Regulations Page 3 of 7
Part III ­ Form 2 (PIBS 4435E Version January 2005)
Drinking-Water Systems Regulation O. Reg. 170/03

June 20/04 UV dose <40 MJ/cm2 Chronic UV June 20/04
AWQI problem being
#27983 investigated by
UV supplier
July 6/04 UV dose <40 MJ/cm2 Chronic UV July 6/04
AWQI problem being
#28870 investigated by
UV supplier
Aug.23/04 UV dose <40 MJ/cm2 Restart UV Aug.23/04
AWQI system put into
#31685 service
Sept 21/04 UV dose <40 MJ/cm2 Restart UV Sept 21/04
AWQI system put into
#33131 service
Oct. 9/04 UVT <80% No unit Restart UV Oct. 10/04
AWQI system put into
#34035 service

Microbiological testing done under the Schedule 10, 11 or 12 of Regulation 170/03,
during this reporting period.
Number Range of E.Coli Range of Total Number Range of
of Or Fecal Coliform of Background/HPC
Samples Results Results Background/ Results
(min #)-(max #) (min #)-(max #) HPC Samples (min #)-(max #)

51 0-21 0-96 8 0-620
Raw
51 0-0 0-0 53 0-1
Treated
158 0-0 0-0 158 0-23
Distribution

Operational testing done under Schedule 7, 8 or 9 of Regulation 170/03 during the
period covered by this Annual Report.
Number of Range of Results
NOTE: For continuous
Grab (min #)-(max #)
monitors use 8760 as the
Samples
number of samples.
Turbidity 8760 0.01 ­ 0.63
Chlorine 8760 0.6 ­ 1.65
Fluoride (If the
DWS provides
fluoridation)

NOTE: Record the unit of measure if it is not milligrams per litre.

Drinking-Water Systems Regulations Page 4 of 7
Part III ­ Form 2 (PIBS 4435E Version January 2005)
Drinking-Water Systems Regulation O. Reg. 170/03

Summary of additional testing and sampling carried out in accordance with the
requirement of an approval, order or other legal instrument.
Date of legal instrument Parameter Date Sampled Result Unit of Measure
issued
mg/L
C of A Suspended Quarterly Annual
5170-5YPP4N Solids Average
(composite) 3.4

Summary of Inorganic parameters tested during this reporting period or the most
recent sample results
Parameter Sample Date Result Value Unit of Measure Exceedance
Jan. 19/04 <0.6 ug/L No
Antimony
Jan. 19/04 <2 ug/L No
Arsenic
Jan. 19/04 13 ug/L No
Barium
Jan. 19/04 9 ug/L No
Boron
Jan. 19/04 <0.1 ug/L No
Cadmium
Jan. 19/04 <3 ug/L No
Chromium
Jan. 19/04 <0.6 ug/L No
Lead (DDW)
Jan. 19/04 <0.1 ug/L No
Mercury
Jan. 19/04 <3 ug/L No
Selenium
April 13/04 4.9 mg/L No
Sodium
Jan. 19/04 0.06 ug/L No
Uranium
Jan. 19/04 0.08 mg/L No
Fluoride
Jan. 19/04 <0.011 mg/L No
Nitrite
Jan. 19/04 0.315 mg/L No
Nitrate

Summary of Organic parameters sampled during this reporting period or the most
recent sample results
Parameter Sample Result Unit of Exceedance
Date Value Measure
Jan. 19/04 ug/L No
Alachlor <0.11
Jan. 19/04 ug/L No
Aldicarb <0.3
Jan. 19/04 ug/L No
Aldrin + Dieldrin <0.067
Jan. 19/04 ug/L No
Atrazine + N-dealkylated metobolites <0.12
Jan. 19/04 ug/L No
Azinphos-methyl <0.21
Jan. 19/04 ug/L No
Bendiocarb <0.13
Jan. 19/04 ug/L No
Benzene <0.36
Jan. 19/04 ug/L No
Benzo(a)pyrene <0.004
Jan. 19/04 ug/L No
Bromoxynil <0.094
Jan. 19/04 ug/L No
Carbaryl <0.16
Jan. 19/04 ug/L No
Carbofuran <0.37
Jan. 19/04 ug/L No
Carbon Tetrachloride <0.34
Jan. 19/04 ug/L No
Chlordane (Total) <0.11
Jan. 19/04 ug/L No
Chlorpyrifos <0.18

Drinking-Water Systems Regulations Page 5 of 7
Part III ­ Form 2 (PIBS 4435E Version January 2005)
Drinking-Water Systems Regulation O. Reg. 170/03

Jan. 19/04 ug/L No
Cyanazine <0.18
Jan. 19/04 ug/L No
Diazinon <0.081
Jan. 19/04 ug/L No
Dicamba <0.17
Jan. 19/04 ug/L No
1,2-Dichlorobenzene <0.56
Jan. 19/04 ug/L No
1,4-Dichlorobenzene <0.25
Jan. 19/04 ug/L No
Dichlorodiphenyltrichloroethane (DDT) + <0.14
metabolites
Jan. 19/04 ug/L No
1,2-Dichloroethane <0.32
Jan. 19/04 ug/L No
1,1-Dichloroethylene <0.52
(vinylidene chloride)
Jan. 19/04 ug/L No
Dichloromethane <1.17
Jan. 19/04 ug/L No
2-4 Dichlorophenol <0.15
Jan. 19/04 ug/L No
2,4-Dichlorophenoxy acetic acid (2,4-D) <0.11
Jan. 19/04 ug/L No
Diclofop-methyl <0.13
Jan. 19/04 ug/L No
Dimethoate <0.12
Jan. 19/04 ug/L No
Dinoseb <0.084
Jan. 19/04 ug/L No
Diquat <1
Jan. 19/04 ug/L No
Diuron <0.087
Jan. 19/04 ug/L No
Glyphosate <6
Jan. 19/04 ug/L No
Heptachlor + Heptachlor Epoxide <0.11
Jan. 19/04 ug/L No
Lindane (Total) <0.056
Jan. 19/04 ug/L No
Malathion <0.091
Jan. 19/04 ug/L No
Methoxychlor <0.14
Jan. 19/04 ug/L No
Metolachlor <0.092
Jan. 19/04 ug/L No
Metribuzin <0.12
Jan. 19/04 ug/L No
Monochlorobenzene <0.46
Jan. 19/04 ug/L No
Paraquat <1
Jan. 19/04 ug/L No
Parathion <0.18
Jan. 19/04 ug/L No
Pentachlorophenol <0.15
Jan. 19/04 ug/L No
Phorate <0.11
Jan. 19/04 ug/L No
Picloram <0.20
Jan. 19/04 ug/L No
Polychlorinated Biphenyls(PCB) <0.04
Jan. 19/04 ug/L No
Prometryne <0.23
Jan. 19/04 ug/L No
Simazine <0.15
Oct.25/04 ug/L No
THM (DDW) 29.75
(NOTE: show latest annual average)
Jan. 19/04 ug/L No
Temephos <0.31
Jan. 19/04 ug/L No
Terbufos <0.12
Jan. 19/04 ug/L No
Tetrachloroethylene <0.48
Jan. 19/04 ug/L No
2,3,4,6-Tetrachlorophenol <0.14
Jan. 19/04 ug/L No
Triallate <0.10
Jan. 19/04 ug/L No
Trichloroethylene <0.54
Jan. 19/04 ug/L No
2,4,6-Trichlorophenol <0.25
Jan. 19/04 ug/L No
2,4,5-Trichlorophenoxy acetic acid (2,4,5-T) <0.14
Jan. 19/04 ug/L No
Trifluralin <0.12

Drinking-Water Systems Regulations Page 6 of 7
Part III ­ Form 2 (PIBS 4435E Version January 2005)
Drinking-Water Systems Regulation O. Reg. 170/03

Jan. 19/04 ug/L No
Vinyl Chloride <0.08

List any Inorganic or Organic parameter(s) that exceeded half the standard prescribed in
Schedule 2 of Ontario Drinking Water Quality Standards.
Parameter Result Value Unit of Measure Date of Sample

(Only if DWS category is large municipal residential, small municipal residential, large
municipal non residential, non municipal year round residential, large non municipal non
residential)

Drinking-Water Systems Regulations Page 7 of 7
Part III ­ Form 2 (PIBS 4435E Version January 2005)

1 Comments:

Blogger FluorideNews said...

New Studies: Fluoride Not Preventing Tooth Decay


New York – March 9 -- Fluoride is not stopping cavities and is causing discolored teeth, is reported in several new studies to be presented at the American Association for Dental Research’s annual meeting from March 8 – 11, 2006, in Orlando, Florida, reports the New York State Coalition Opposed to Fluoridation (NYSCOF).



For example:



-- Researchers following children from birth, starting in 1991- 1995 (Iowa Fluoride Study), found almost double the dental fluorosis in early erupting permanent teeth of 9 year-olds drinking optimally fluoridated water compared to children drinking sub-optimally fluoridated water (41% vs. 21%); but no less tooth decay.(1)



-- Researchers found no significant relationship between fluoride exposure and cavities in permanent teeth of 6 to 9-year-olds in Campeche, Mexico(2). Previously, it was reported that 56% of this group has dental fluorosis.(3)



-- A U.S. national study reports cavity prevalence increased by 15% in 2 to 5-year-olds, in surveys taken between 1988-1994 and 1999-2002,(4) despite 60 years of water fluoridation reaching 2/3 of Americans on public water supplies and virtually 100% via the food supply. However, the Centers for Disease Control report that 1/3 to 1/2 of U.S. schoolchildren display dental fluorosis.(4a)



-- Another U.S. study shows that breastfed children have less cavities than non-breastfed.(5) even though breast milk has 100 times less fluoride than dentists claim is optimal to reduce cavities. Breastfeeding is also protective against fluorosis.(5a)



-- Although New York City fluoridated in 1965, NYC children of Chinese descent suffer a much higher prevalence and severity of tooth decay than the national average (63% vs 38%). (6)



-- About half of 7 to14-year-old children from fluoridated Rochester, NY, have cavities. Latino children had significantly higher caries experience than African-American and Caucasian children, thus indicating that disparities exist among different ethnic groups even when the water is fluoridated.(7)



-- In fluoridated Detroit, 91% of African American low-income children, 5 years and younger, have tooth decay.(8)



“Today, fluoridation puts American children at risk of dental fluorosis without any benefit of less tooth decay," says Paul Beeber, NYSCOF President and General Counsel. "And growing evidence links fluoride to hypersensitivities, bone damage, thyroid problems and more," says Beeber.



These studies add to a growing body of evidence pointing to fluoride's ineffectiveness and lack of safety: See: http://www.fluoridealert.org/health/teeth/caries/fluoridation.html#top





Contact: Paul Beeber, nyscof@aol.com



www.orgsites.com/ny/nyscof

www.FluorideAction.Net





SOURCE: NYS Coalition Opposed to Fluoridation, Inc

PO Box 263

Old Bethpage, NY 11804

References:



(1) AADR 35th Annual Meeting in Orlando:
Abstract # 0153 - Dental caries and fluorosis in relation to water fluoride levels, I Hong, SM Levy, J Warren, B Broffitt http://snipurl.com/n8hg



(2) AADR 35th Annual Meeting in Orlando:

Abstract # 1995 - Cross-Sectional analysis of dental caries in children with mixed dentition, AA Vallejos-Sanchez, CE Mendina-Solis, JF Casanova-Rosado, G Maupome, AJ Casanova-Rosado, M Minaya-Sanchez http://snipurl.com/n8i9



(3) Prevalence of dental fluorosis and additional sources of exposure to fluoride as risk factors to dental fluorosis in schoolchildren of Campeche, Mexico, PR Beltran-Valladares, H Cocom-Tun, JF Casanova-Rosado, AA Vallejos-Sanchez, CE Medina-Solis, G Maupome, Rev Invest Clin. 2005 Uly-Aug;57(4):532-9

http://www.ncbi.nlm.nih.gov/entrez/query.fcgi?cmd=Retrieve&db=pubmed&dopt=Abstract&list_uids=16315637&query_hl=1&itool=pubmed_docsum



(4) AADR 35th Annual Meeting in Orlando:

Abstract # 0458 - Trends in Dental Caries of Primary Teeth, United States, 1988-2002, F Jaramillo, E Beltran, L Barker, S Griffin, Centers for Disease Control and Prevention http://snipurl.com/n8jq



(4a) Beltrán-Aguilar et al. Surveillance for Dental Caries, Dental Sealants, Tooth Retention, Edentulism and Enamel Fluorosis – United States, 1988-1994 and 1999-2002. MMWR. CDC August 26, 2005

http://www.cdc.gov/mmwr/preview/mmwrhtml/ss5403a1.htm





(5) AADR 35th Annual Meeting in Orlando:

Abstract # 0881 - No association between breastfeeding and early childhood caries: NHANES 1999-2002, H Iida, P Auinger, M Weitzman, RJ Billings http://snipurl.com/n8jw



(5a) Breastfeeding is Protective Against Dental Fluorosis in a Nonfluoridated Rural Area of Ontario, Canada, D Brothwell, H Limeback, Journal of Human Lactation, Vol. 19, No. 4, 386-390 (2003) http://jhl.sagepub.com/cgi/content/abstract/19/4/386

(6) AADR 35th Annual Meeting in Orlando:

Abstract # 0l50 - Caries Experience among Chinese-American Children and Adolescents in Lower Manhattan, CH Chinn http://snipurl.com/n8k9



(7) AADR 35th Annual Meeting in Orlando:

Abstract # 0478 - Dental Caries in Latino Elementary School Children, S Gajendra http://snipurl.com/n8lz



(8) AADR 35th Annual Meeting in Orlando:

Abstract # 1992 - Severity of Dental Caries Among African American Children in Detroit, AI Ismail, M Tellez http://snipurl.com/n8m2





Fluoridation News Releases
http://tinyurl.com/6kqtu

7:03 AM  

Post a Comment

<< Home